How does the RTL valve for radiant heating systems work?
Controlling the surface temperature using the RTL principle (RTL = return temperature limiter) is a well-established control technique. It is particularly well suited when additional underfloor, wall or ceiling heating is to be retrofitted into an existing heating system with higher flow temperatures.
The RTL valve continuously measures the heating water temperature in the heating circuit. If this is too high for the surface heating (the maximum settable temperature is around 45°C; the usual operating temperature for low profile systems is between 30 and 35°C), the valve interrupts the flow through the heating circuit and no further heating water flows in. Consequently, the water in the heating circuit cools down to the set temperature. If the temperature falls below the set temperature for the surface heating, the RTL valve reopens the flow. This reliably prevents the retrofitted heating circuits from overheating. We explain the technical operation in detail, using the deployed RTL boxes as examples.